It’s nice to know that your UPS has a long warranty, and you’re safe in the knowledge that if anything goes wrong with it, the manufacturer will repair it for you free of charge. However this warranty generally covers only the electronic side of the unit, and does not include the batteries and in some instances the fans.

This leads to a bit of an issue. Let’s say your UPS has been working for a couple of years and then stops working. You send it back to the manufacturer who fixes it under warranty but will charge you for replacement batteries as well. Nothing wrong with that provided the batteries required replacing, or indeed since a UPS is only as good as it’s batteries then it’s good to know your batteries are in tip top condition. However the issue here is that the UPS did not last five years before you had to pay to get something done to it.

It’s also a good idea to check the batteries on your UPS regularly and perform a quick test on the UPS to ensure all is well. Most UPS will sit there quite happily with defunct batteries and you will only find out they are defective when you come to use them. This is especially poignant just as the battery warranty is due to expire. The manufacturer will generally offer a two year warranty on the batteries. With normal use standard lead acid batteries should last up to about 5 years. If they get warm or have been used regularly this life time diminishes. Generally speaking three years is to be expected.

Also, visually inspect your batteries if you can. If they are swollen or misshaped at all, this is a problem with the UPS battery charge circuit and nothing to do with defective batteries. Do not pay the manufacturer to change these batteries. If in doubt, contact the manufacturer of the battery concerned for advice. Provided the battery has not bee physically damaged, or kept in an oven the main cause for battery swelling is “overcharging, excessively high recharge current”, which is a (design) problem with the UPS.

 

Our VIX series of Uninterruptible Power Supply has an in-built auto-switch off function when it detects a low load on the output when on battery power. If the load is under around 30W, then the batteries do not discharge correctly and as a result they may become “deep discharged”. Batteries that have been subjected to a deep discharge cannot be recovered from this state.

This is an important feature in order to preserve battery life. The UPS constantly monitors the battery voltage during an outage looking for the tell-tale signs of end of discharge, when the terminal voltage on the battery begins to fall away. If the load drawn from the battery is light, then the battery voltage does not drop away as predicted and as a result, the batteries can become severely depleted and are likely to become defunct.

For example, assume that your PC is turned off, and you get a power cut. The UPS without this feature would switch to battery power and end up draining the batteries for no good reason and potentially rendering the UPS useless. This situation is avoided by switching off the UPS during battery operation after about a minute, ensuring that the batteries are maintained in a healthy state.

If your application has a naturally low load, then you are at risk of shortened battery life without this feature. If you’re using the VIX series then the simplest solution is to increase the load to around 50W or so.

I’ve mentioned in other posts that runtime is battery. On our websites we use calculated values to determine the runtime based on a particular load. The purpose of this post is to give you an understanding of this process.

The first thing you need to know is that battery discharge is non-linear. For those of you who don’t understand the expression I’ll elaborate. A linear expression is one where, for example, you put two in, you get four out. So it follows that if you put three in, you get six out, or you put five in, you get ten out. EG. whatever you put in  you get twice out. In the non-linear world this doesn’t hold true, for example, you put two in, you get four out, but when you put three in, you get nine out etc.. This non-linearity makes the discharge characteristics very difficult to express mathematically.

Luckily, the battery manufacturers provide us with discharge tables that we can look up, but first we need to know some information about the UPS, the load and about the method.

End of Discharge Point

At what point will the UPS switch off? Your normal 12V lead acid battery contains 6 cells each of a nominal voltage of 2V (so you get 6x2V=12V). In practice the voltage is slightly higher than this and reduces as the battery is discharged. It is important not to allow the battery to become too discharged, so the UPS will monitor the cell voltage and cut off when it gets to a predetermined point. This is usually around 1.7V per cell or 10.2V for 12V battery.

UPS Efficiency?

Well, more precisely, the inverter efficiency. The inverter is used to convert the battery DC power into AC power. There will be losses associated with this. The better the inverter, the lower these losses are. If you’re unsure, use a worst case of say, 80% efficient. This means that for every 100W provided to the load, the batteries will need to provide 125W (simply 100/efficiency).

The Load Power Factor

Is the load purely resistive, or does it have a power factor? We’re only interested in the amount of WATTS that are needed.

Amps or Watts Method?

Firstly, there are two methods for calculating runtime, the Amps method, or the Watts per Cell Method. Generally, Watts per Cell is used for short term discharges and Amps is used for long term discharges.

Process

It’s easier to do this with an example, so let us take a standard server type load with a number of ancillary devices. We know from measurement  that the Ampere draw is 7Amps and we have mains voltage of 235V. Our Watts therefore (assuming unity power factor) is 1645W.

Our UPS has an inverter that is rated at 90% efficient, so the amount of power from the battery required to deliver 1645W is 1645/0.9 = 1828Watts.

Our UPS is a 3KVA, 2.1KW UPS that contains 8 batteries connected in series. Each battery is rated at 12V 7.2 Ah.

 I now need to look up the manufacturers data sheet and I find the following for a 7.2Ah battery:

Constant Current Discharge
F.V. 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 28.6 18.6 14.3 8.75 5.28 3.06 2.18 1.72 1.42 0.930 0.760 0.400
1.67V 26.8 17.9 13.9 8.69 5.27 3.05 2.17 1.71 1.41 0.930 0.753 0.386
1.70V 26.0 17.6 13.8 8.67 5.26 3.05 2.17 1.71 1.41 0.930 0.750 0.380
1.75V 24.3 16.8 13.3 8.55 5.24 3.03 2.16 1.71 1.41 0.925 0.740 0.370
1.80V 22.5 16.0 12.8 8.42 5.22 3.00 2.15 1.70 1.40 0.920 0.730 0.360
1.85V 20.8 15.2 12.4 8.30 5.20 2.98 2.14 1.70 1.40 0.915 0.720 0.350
Constant Power Discharge
F.V. 5MIN 10MIN 15MIN 30MIN 1HR 2HR 3HR 4HR 5HR 8HR 10HR 20HR
1.60V 57.16 37.16 28.5 17.5 10.56 6.1 4.36 3.45 2.83 1.86 1.51 0.79
1.67V 53.5 35.83 27.83 17.33 10.53 6.06 4.35 3.43 2.81 1.85 1.5 0.77
1.70V 52 35.16 27.5 17.33 10.51 6.05 4.33 3.43 2.81 1.85 1.49 0.76
1.75V 48.5 33.66 26.66 17.16 10.48 6.03 4.31 3.43 2.81 1.83 1.47 0.74
1.80V 45 32 25.66 16.83 10.43 6 4.3 3.41 2.8 1.81 1.45 0.71
1.85V 41.5 30.5 24.83 16.66 10.4 5.98 4.28 3.41 2.8 1.8 1.43 0.69

Constant Power Discharge Method 

Our battery load is 1828W and we have 6×8=48 cells. Therefore our Watts per Cell is 38Wpc.

We know the FV (Final Value or End Of Discharge Point) is 1.7Vpc so looking along the Constant Power Discharge Table, we can see that 52Wpc would give 5 minutes, so we will get more than 5 minutes runtime. We can see that 35.16Wpc would give 10 minutes runtime, so we will get less than this.

So the calculated runtime for this example, based on constant power discharge is between 5 and 10 minutes.

 Constant Current Discharge Method

We have a total of 8x12V batteries in series, giving us a string voltage of 96V. We need to deliver 1828W so our Amperage is 1828/96 (from Power=VoltsxAmps, so Amps=Power/Volts). = 19Amps.

Now looking along the table above in the Constant Current Section, with our FV of 1.7, we see that a 26A discharge would give us 5 minutes, so we will get longer than this. A 17.6Amp discharge would give 10 minutes, so we will get less than this.

Therefore using the constant current discharge method we will get between 5 and 10 minutes runtime.

Working it out in reverse – I want 2 hours runtime – how many batteries do I need?

Using Watts Per Cell Method.

From the table under Constant Power Discharge, we can see that for our FV of 1.7, for a 2 hour runtime we need to have a WPC discharge of no more than 6.05. Our load is 1828W, so we need 1828/6.05 = 302 cells, which is 50.35 batteries. The battery requires a 96V string voltage, based on banks of 8, so we will require 6 banks to get close (that is 48 batteries), or 7 banks to be sure (that is 56 batteries).

Using Constant Current Method.

From the table above under Constant Current Discharge, you can see for our FV of 1.7V we need to have no more than a 3.05A discharge from each of our batteries to achieve a 2 hour runtime.

Our total current draw is 1828/96 = 19Amps (1828Watts load/Battery String Voltage = 96V)

Dividing the 19Amps total current by 3.05 gives us the number of strings needed to achieve 2 hours runtime which is 6.24. Obviously we cannot add in a quarter of a string so we need to round up. In this case we require 7 battery strings, or a total of 56 batteries to achieve a runtime of 2 hours.

Alternatively, you could of course opt for higher capacity batteries, and maintain the same number of batteries. The examples above were using 7.2Ah lead acid batteries but there are other choices available.

© 2012 The Power Protection Blog Uninterruptible Power Supply