An isolation transformer is used to create a power source that is not electrically, but magnetically, connected to the source. It is primarily used for electrical safety where any exposed electrical conductor can be touched without the risk of electric shock. In certain circles, the isolation transformer is heralded as an answer to power quality issues and this article is intended to highlight why this is not and cannot be the case by a detailed technical look at the claims made by some power quality specialists.

History

Putting isolation transformers into a UPS system is not new. In fact, some technologies relied on the transformer to create the power waveform (ferro-resonance). In most cases the need for the transformer was due to it’s ability to step up an AC voltage. This allowed an inverter to output a low AC voltage due to limitations on the voltage capacity on the power electronic components. More recently advances in power electronics have enabled the transformer to be removed and the inverter output connected directly to the load. This is called a high frequency design and is the basis for modern online double conversion UPS.

The ½V 10V Myth

Some UPS manufacturers include an  isolation transformer to allow the Neutral to be bonded to the earth thereby creating a new N-E bond and eliminating any Neutral to Earth Voltage. Claims have been made that common mode voltage (and that means a voltage referenced to a common source – in this case the ground or earth conductor) of over ½V or normal mode (between live and neutral) of over 10V can cause equipment malfunction.

However, Neutral to Earth voltage does not cause malfunction with modern electrical equipment. This can be easily demonstrated by going to Germany and plugging something into the wall socket. You can then unplug it, turn the Schuko lead around by 180 degrees and plug it in again. Hey presto, what was once live is now neutral and vice versa and guess what – the electrical equipment works just the same without any problems at all, despite the neutral to earth voltage being 230V. Or you could simply rewire your mains lead to demonstrate.

In the UK, the neutral and earth are bonded at the consumer unit in any case, and any significant N-E voltage is an infra-structure issue that would require addressing by an electrician. Now perhaps such claims were meant for higher frequencies and so the use of the isolation transformer is to eliminate noise, after all I’ve heard such claims that the isolation transformer “removes noise from the earth, and since many electronic devices use earth as a logic reference any noise of over ½V here can cause logic errors“. Noise on the earth is a misleading phrase. Electrical Noise is simply a high frequency voltage which is measured between two points. You cannot have noise on the earth in isolation, it must be between earth and some other point and in this case the claim is between Neutral and Earth.

This would mean that for any malfunction to occur with as little as ½V of N-E noise, the Neutral conductor must, in some way be used within the logic of the electronic apparatus. Now many years ago this could have been the case, but nothing manufactured over around the last 20 years would have this drawback. Electrical safety standards require that the Live & Neutral conductor are separated from the earth with a high degree of isolation (tested at up to 3000 Volts). To do this they use internal isolation. All computer devices use DC power derived in the main from a device known as a switched mode power supply (SMPS). This contains an isolation transformer which operates at a high frequency which allows it to be substantially smaller than a mains frequency equivalent. The output DC logic levels of the SMPS are completely isolated from the input AC Live and Neutral conductors. Devices that do not utilise SMPS often use rectifiers from a low level AC source, derived from a step down isolation transformer.

This internal isolation negates the need for an external isolation transformer as Neutral to Earth Noise on the input cannot propagate to the DC levels used by the computer logic except in extreme cases.

This is not to say that noise on the AC power line can not cause problems, but there are other ways of addressing this such as simple filtering or improved earthing. The isolation transformer also requires additional filtering to deal with noise and is effective only as a filter in this scenario. The EMC directive has also required equipment to be more robust to the effects of electrical noise.

Schuko Lead

The Schuko Lead. Proof that N-E Voltage isn't an issue.

Voltage Regulation

An issue with transformers is that they have an output voltage that is dependent upon the loading on the transformer. This is called Regulation. The output voltage of an isolation transformer under no-load is higher than the output voltage under full load.

This causes the terminal voltage to vary with changing loads. It also means that there is the potential to have dangerously high or too low voltages on the output. The input and output voltages of a transformer are dictated by the ratio of the number of windings on the primary side to the number of windings on the secondary side. In order to overcome the regulation issue with transformers operating at close to their capacity is to slightly step up the voltage. This is so as the transformer becomes loaded, the output voltage falls. So for a 230V input at 0% load, the output may be a few % higher than a nominal, and at 100% load the output would be a few % lower. How big this % is depends upon how good the design of the transformer is. The problem is, if your input voltage is on the high side (the specification for the UK is 230V±10%, so that could be 253V) adding a few % more makes the output voltage dangerously high and may cause equipment damage. Equally if your mains voltage is on the low side (207V) then a few % lower may cause your equipment to stop operating.

Some UPS overcome this with buck and boost circuits, however I have known for the output voltage from a transformer based UPS, even with a buck function to be at 260V.

RCDs Don’t Trip

It is perhaps one of the most disturbing aspects that many people installing a power protection device containing an isolation transformer are unaware that any residual current device that was put into the infrastructure to provide fast disconnection in the event of a fault will not operate. Of course, large fault currents as created during short circuits will cause other protection measures to operate, but small fault currents that RCDs are designed to protect against will not cause the RCD to trip.

This is because an RCD operates by detecting an imbalance between the Live and Neutral conductors. Since the isolation transformer isolates the secondary side from the primary, any fault current to earth -no matter how large- causes no deviation from the incoming Live and Neutral current balance as the fault current loop (secondary Live to earth) is contained entirely within the secondary side of the transformer.

This is, in fact, why isolation transformers are used for safety, and are also used in critical power applications such as operating theatres, intensive care wards and chemical plants etc., where an earth fault should not cause disconnection of the supply, and ensures that personnel are safe from electric shock even with a fault. However, this is only true if the output conductors are floating with respect to earth, that is, there is no Neutral to Earth Bond.

If your infrastructure has your circuit protected with an RCD due to the risk of electric shock caused by low fault currents (as recommended where water is nearby) then you should be aware that the RCD will never operate.

This drawback is used however for other purposes – where there is a requirement to remove earth leakage and this is one of the situations where the isolation transformer comes into it’s own.

Power Conditioning

It is interesting to note that for all the recognised power quality problems as defined by the Leonardo Power Quality Initiative (http://www.leonardo-energy.org/) not one of the solutions recommends the use of an isolation transformer. This despite the fact that UK Copper Development Association is one of the members and has some great guides on power quality http://www.copperinfo.co.uk/power-quality/power-quality-guide.shtml that again do not call for the use of an isolation transformer.

In fact, most power quality issues that are noise related can be addressed with improved earthing and many other problems such as harmonic content cannot be addressed with isolation transformers.

Ground Loops

A ground loop is where an earth current flows from one earthed point to another usually through some unexpected path such as data lines and causes malfunction and damage. Now an isolation transformer can stop a ground loop for one piece of attached equipment, if the earth is isolated and the output left floating. You could of course, just cut the earth wire which would have the same effect but this of course is electrically unsafe. As discussed above the isolation transformer can be used for safety purposes and this how in can be used in this context to prevent a ground loop from occurring by effectively disconnecting the earth.

However, if the isolation transformer has the earth straight through, as is the case with transformer based UPS then ground loops will not be prevented.

Transformer Hum

Transformers are known to hum and this is due to poor construction, poor AC power quality or both. Transformer hum increases inefficiency and is of course annoying.

Succesful Trials

One of the methods of selling a power quality solution is to offer to trial and see the benefits. This is all well and good but is not particularly scientific. Personally I knew one large corporation who spent millions of pounds on transformer based power protection solutions due to a successful trial. However this trial was not without it’s critics, who suggested to me that the problem with the trial is that they were comparing doing nothing with fitting one type of power protection solution. Other avenues to address their power quality issues were not explored.

The key is to understand what power quality problems exist and how to eradicate them effectively.

Demonstrations

I’ve witnessed demonstrations of power quality improvements using bespoke equipment that prints out endless reams of paper, and by using an oscilloscope display attached to some sort of box connected to the mains supply. You can flick the lights on and off and wow, an endless stream of spikes appear on the oscilloscope. You then put an isolation transformer based power protection solution in the way, flick the lights on and off again and lo and behold this time no spikes.

It’s a fairly impressive demonstration but has some serious flaws. The first one is fairly obvious. If all these damaging spikes occur just by switching on the lights, then surely computers would be falling over up and down the country. There’d be outcries against manufacturers producing substandard equipment that is susceptible to a light switch.

I’m  not saying these spikes are not there, but they’re not what they are made out to be. The intensity of them is extremely low, and they carry no destructive threat. The reason you can see them is because you’re viewing through a very high impedance source of over 1M?. Add any sort of load to the output and you would see these spikes disappear. They’re a bit like radio signals and don’t do anything.

Another concern is that nobody knows how this magic box works. Is it active or passive? Is it amplifying any signals that happen to be there, and if so by how much? Does 1V noise on the oscilloscope equate to 1V noise on the mains? Is it calibrated? If so, how and by who?

That said, you can clearly see the isolation transformer remove the apparent noise, showing that it is doing something. However I’ve also seen the same effect using nothing more than a transorb costing a few pence in a device created by a rival power protection firm.

Like the trials, it is an understanding of real power quality issues that is required.

Switching On Lights - Power Quality Issue?

Switching On Lights - Power Quality Issue?

International Standards on Power Quality

There are several international standards that deal with power quality problems and acceptable limits. Not one of these standards raises a concern about a half volt of electrical noise on the mains supply. Power monitoring equipment manufactured by some of the most respected test equipment manufacturers does not contain measurement tools for such levels of noise either.

It begs the question where do these limits come from? The answer goes way back to a conference in California some time in the 1980′s to do with semiconductor test equipment. It was a paper that was presented and that’s it. There has been no recognised international standard written to endorse or otherwise substantiate the claims presented in that paper.

About Me

I started my UPS career with a company specialising in isolation transformer based power protection solutions. After several years I moved to a competitor company and spent several more years there. I was an isolation transformer fan. As a degree qualified engineer I was never comfortable with the “smoke and mirrors” demonstration and never demonstrated it, instead focussing on the benefits of power protection per se and how the isolation transformer can help overcome these issues. I left the organisation and got another view of the world and started to question the validity of these power protection claims. I have come to the conclusion that the isolation transformer has it’s place as a power protection solution but that there are other technologies that provide better level of protection at a fraction of the cost. Transformerless Online Double Conversion UPS provide protection that is more than adequate for 99.9% of applications, covering all recognised power quality issues.

At my company we provide excellent power protection solutions for a wide variety of applications, from simple battery backup solutions to small data centres in lightning prone Sierra Leone.

As mentioned in this article, education is the key and we’re open and honest about technology and what is can and cannot achieve.

It’s nice to know that your UPS has a long warranty, and you’re safe in the knowledge that if anything goes wrong with it, the manufacturer will repair it for you free of charge. However this warranty generally covers only the electronic side of the unit, and does not include the batteries and in some instances the fans.

This leads to a bit of an issue. Let’s say your UPS has been working for a couple of years and then stops working. You send it back to the manufacturer who fixes it under warranty but will charge you for replacement batteries as well. Nothing wrong with that provided the batteries required replacing, or indeed since a UPS is only as good as it’s batteries then it’s good to know your batteries are in tip top condition. However the issue here is that the UPS did not last five years before you had to pay to get something done to it.

It’s also a good idea to check the batteries on your UPS regularly and perform a quick test on the UPS to ensure all is well. Most UPS will sit there quite happily with defunct batteries and you will only find out they are defective when you come to use them. This is especially poignant just as the battery warranty is due to expire. The manufacturer will generally offer a two year warranty on the batteries. With normal use standard lead acid batteries should last up to about 5 years. If they get warm or have been used regularly this life time diminishes. Generally speaking three years is to be expected.

Also, visually inspect your batteries if you can. If they are swollen or misshaped at all, this is a problem with the UPS battery charge circuit and nothing to do with defective batteries. Do not pay the manufacturer to change these batteries. If in doubt, contact the manufacturer of the battery concerned for advice. Provided the battery has not bee physically damaged, or kept in an oven the main cause for battery swelling is “overcharging, excessively high recharge current”, which is a (design) problem with the UPS.

 

All Uninterruptible Power Supply or UPS Systems consist of a rectifier which converts your normal mains AC power into DC power, an inverter that converts DC power into AC power, and an energy storage medium which is usually lead acid batteries.

There are 3 main UPS technologies – Offline, Line Interactive and Online Double Conversion – and two different types of inverter – square wave (also called pseudo-sine wave or modified sine wave) and sine-wave.

An Offline UPS provides basic levels of power protection. There is usually a degree of surge suppression incorporated and when the input mains voltage goes out of tolerance (that is too high/low or fails) the UPS inverter starts up and provides power to your equipment. There is a break in the mains supply when this occurs in the region of 10-20 thousands of a second which will generally go unnoticed by the majority of equipment. The inverter in offline UPS is nearly almost always a square wave.

A line interactive UPS is similar to an offline UPS but has the added benefit of voltage regulation. This means that it will reduce the mains voltage if it goes too high (called “buck”) or raise the mains voltage when it goes too low (called “boost”). It will do this without reverting to battery and hence conserve battery life. Since a line interactive UPS has an inline transformer, it also provides in-built filtering and hence a higher degree of power protection. Like the offline types, there is also a break during the transition from mains power to battery power. In higher quality line interactive units, this break may be as low as only 2 to 4 thousandths of a second. Line Interactive UPS Systems come with square wave as well as sine wave inverters.

The online double conversion UPS System is considered by many to provide the highest levels of power protection. The inverter is always on, and provides power to the load. This means that there is no deviation in output voltage and no break if the UPS reverts to battery power. The output waveform in an online UPS System will almost always be a sine-wave, generally of very high quality and can enhance the operation of certain equipment. An online double conversion UPS also has a bypass circuit, which allows power to be continually fed to your load even if the UPS develops a fault or is overloaded.

In choosing your technology you need to consider:

  1. The power consumption of your load
  2. The type of load you have
  3. How critical your load is
  4. The environment in which the UPS will sit
  5. The required runtime
  6. Your budget

Your normal UK socket outlet is rated at 13Amps which means the most power you can draw from a UK outlet is 3KVA, or 3KW. (Power Measurement will be covered in a separate paper). Above this level (for specialist equipment, or hardwired installations) most UPS will be online double conversion technology as the economies of scale start making other technologies non cost effective. Below this level, however all technologies are available, although above around 2KVA, line interactive systems start to become heavy and unwieldy due to the size of transformer that is required.

If your load is made up of computer type power supplies, then both square wave and sine wave products will power this equipment adequately. If your load contains motors, transformers, pumps or other inductive components (on the input power supply) then square wave systems are not suitable and you must opt for a sine-wave system.

Any load that is susceptible to mains disturbances such as in analytical equipment or audio applications should also choose a sine-wave system. Where mains distortions affect equipment performance then you need to opt for online double conversion where a pure sine-wave is always present.

If your load is critical for operation then the increased benefit of online double conversion technology should be used. This provides additional security against all power disturbances as well as the comfort of a fall-back bypass in case a fault develops with the UPS. You may wish to parallel together UPS and again, this can only be achieved with online double conversion UPS. (We’ll cover parallel systems and redundancy in a separate paper). If you have a PC where you are looking for simple battery backup to stop annoyance rebooting or tripping then an offline or line interactive unit would suffice.

Offline and line interactive UPS Systems are generally quiet in operation and do not utilise cooling fans in normal operation (usually). This means they are suitable to be placed in an office or home environment. Online Double Conversion UPS systems require forced cooling and can be quite noisy and therefore tend not to be suitable for use in an office environment.

If you are running your UPS in conjunction with an emergency backup generator then the benefits of online double conversion technology come to the fore, as the UPS will cover for any transition to generator operation and also provide a constant unchanging power source during generator start up and any shifts that may occur in frequency and or voltage during load switching.

Offline UPS tend to be the smallest of all technologies so can be useful to provide emergency ride through for areas where space is at a premium.

Long runtimes on UPS are better handled with online UPS Systems. This is because they are designed to operate continually from the inverter. In which case it does not matter if the input power is from the rectifier or the battery – the operation is the same. Offline and Line Interactive units tend not to be designed for this continuous operation. (Battery selection and runtime will be covered in a separate paper.) It is also unwise to power any equipment with a square wave inverter for any prolonged period of time as you could cause degradation to electronic components. Square wave systems are designed to allow basic computer systems to ride through brief power outages or time to shut down a system in the event of a prolonged power cut.

You may have already made up your mind which technology you need, but let’s take a look at relative costs. Offline UPS systems used to be by far the cheapest. However nowadays an offline UPS and a line interactive square wave unit are typically similar prices. Online Double Conversion used to be far more expensive than other technologies, but now is comparable to a high quality sine-wave line interactive UPS.

With regard to running costs, the offline UPS is the most efficient as in normal operation the input power goes straight through to the load, so the only power loss is to keep the battery float charged and power the UPS logic. Line Interactive units are similar in efficiency but experience more losses due to the transformer required for the buck and boost facility. Online Double Conversion however, has the drawback of being the least efficient of the technologies.

In summary, for simple low cost battery backup then the offline or line interactive square wave systems are suitable. For high grade protection in a quiet environment, or where your load type demands it, opt for a sine-wave line interactive unit. However, if you want the best power solution, then we recommend online double conversion technology as it is compatible with all load types and provides the highest degrees of power protection.

Scarborough based Dale Power Solutions are putting pen to paper on a series of articles on UPS System and Generator technologies and applications. The series will be published regularly over the forthcoming weeks. The first paper entitled “Which Uninterruptible Power Supply Technology Do I Require?” focuses on the differing UPS technologies and how these relate to your particular application, provided in a no-nonsense and jargon free language.

The first paper is available to view online now at www.dale-online.co.uk/help.php, and further papers will be added when released, so check back regularly for the full series.

When we’re talking about UPS systems we are talking here about Uninterruptible Power Supplies that generate AC power. There are basically two types, rotary and static.

Rotary Systems
Traditionally rotary systems are so called as they basically are a motor-generator. In a nutshell, the incoming mains powers a motor that spins a flywheel that then powers the generator. When the mains goes, the flywheel keeps the generator part going. This may be supplemented with Lead Acid batteries to extend the run time. Lately I’ve heard UPS called rotary systems because they use flywheel technology as the energy storage mechanism, but this strictly isn’t correct. Rotary systems are typically used for large installations, and are particularly suited where you have mechanical loads that demand high inrush currents.

Static UPS Systems
Are so called as they don’t have any moving parts and generate AC by what is known as an inverter. With static systems these are divided into basically three technologies, offline or standby, line interactive and online or double conversion systems.

Offline UPS:
The basic UPS system. What goes in goes out except when the mains supply goes out of tolerance, that is lower than about 207VAC or higher than about 253VAC. When this happens, AC is produced by an inverter. However this AC waveform is 99% of the time non-sinewave. Sometimes called square wave or pseudo-sine wave, it’s basically non-sine. These systems are cheap and cheerful and used for low grade protection of non-essential equipment, such as the odd PC where loss of data is more of an inconvenience than anything else. According to the new classification of UPS EN64020, these systems are VFD. These are available upto about 3KVA, but in fairness I’d stick to a max of about 1KVA for a PC or so.

Line Interactive:
There’s a lot of confusion as to what line interactive is. I’ve heard that a line interactive unit has to have a sinewave inverter, or that it contains a common charger/inverter so that the inverter is “alive” all the time and so reduces transfer time, or that the UPS will interact with the (power) line to keep the voltage within tighter limits. Well, the standard EN64020 has kind of defined the latter as line interactive or VI (Voltage Only Independent). So basically, any system that provides a degree of voltgae regulation is therefore line interactive. However this really only adds to the confusion as there is now a huge gulf in technology of line interactive units. Take the MiniGuard on this UPSMart shop. It’s line interactive as it provides voltage regulation and has a square wave output. The manufacturer (Kehua) market it as an Offline product (which is correct in my view). APC define their line interactive units as those with a common charger/rectifer and so distinguish the technology and hence price between their Backups and Smartups series. Both may now be defined as line interactive. Just check the price difference – again on this site- between the Opti – PS series – a high end line interactive product and the Mini Guard. Luckily the EN64020 standard does have some other means of defining using a series of letters and numbers after the initial classification, but who really will understand this? There’s no easy answer really, but take advice and read the specs for any line interactive unit.

Line Interactive systems are generally available upto around 3KVA, although 5, 7 and even 10KVA units are available. There advantage is that they are highly efficient, as the only power conversion is done when the unit is on battery. They are a good mid choice of technology. Disadvantage is that at higher power rating they tend to become very heavy due to the need to include a transformer for the voltage regulation, and a better bet is to opt for online technology.

Online UPS
Considered by many to be the only “true” form of a UPS. The input power is rectified (or converted) to DC which creates a DC buss that feeds the inverter. The inverter then converts the DC back into AC. As you can see, there are 2 conversions, hence the term “double conversion”. The obvious draw back here is efficiency, but the advantages are a very wide input voltage window (some systems will even except 100V without reverting to battery), a stable, clean output power waveform, and protection against practically all power problems. Online UPS also contain a bypass line, which means, in the event of UPS failure or overload, the system will divert power from the inverter back to the mains, and back again if the problem is removed, thus ensuring higher availability.

Online technology is the mainstay of all UPS systems above 10KVA, and is available from around 700VA. It is used for the protection of systems that are critical in nature. Traditionally expensive, the prices are now becoming competitive and overtaking line interactive as the preferred choice of mid level protection. I’ve seen here at UPSMart, a 1KVA online cheaper than any high grade line interactive unit. So unless you want higher efficiency or are in a very quiet environment than I’d opt for online units everytime. (note – online systems are “online” all the time and use forced cooling to keep them from overheating. This of course generates fan noise).

The new standard determines online units as VFI, where both the Voltage and Frequency are Independent.

I guess there’s a lot of text here, but I hope it makes sense. Just add a comment if you want clarifiation or disagree with anything said here.

© 2012 The Power Protection Blog Uninterruptible Power Supply